Free hot gas volume calculator: convert normal flow in Nm3/hr to actual m3/hr at your flue gas temperature, and see the usual blower material from 20 to 650 °C.
Hot gas volume calculator
Hot gas takes up more room. Enter the flow at normal conditions and the gas temperature, and see the actual volume the fan has to move and the material usually used at that temperature.
*Indicative only. Actual volume = normal volume × (273 + gas temperature) ÷ 273, at the same pressure. Real selection also depends on gas density and composition, altitude, duct resistance and the fan curve, so we size every fan from your duty data.
How the number works
Gas expands when it is heated. The actual volume equals the normal volume multiplied by (273 + temperature) divided by 273, at the same pressure.
A fan moves a volume, not a mass. A hot gas stream of the same mass is a much bigger volume, so the fan must be bigger.
Normal conditions are a fixed reference (Nm³/hr). Actual conditions are what the fan really sees at its inlet (m³/hr).
The temperature also decides the material and the bearing arrangement, so the calculator shows the usual choice.
What it leaves out
Gas density and composition, altitude, duct and furnace resistance, and the fan curve all decide the fan. That is why we size every fan from your duty data and ask for a layout sketch.
Before we quote
Do not worry if you do not have all of them. Send what you know, and our engineers will ask for the rest.
Hot air, flue gas or process gas, with its composition if it is corrosive, wet or dusty.
Normal and peak gas temperature at the fan inlet.
Volume in m3/hr or Nm3/hr, and whether it is at actual or normal conditions.
Static pressure the fan must develop, or the duct and furnace resistance.
Induced draft, forced draft or recirculation, number of fans, standby needs.
Power supply, space limits, a layout sketch, fuel and any CPCB or safety requirements.
Engineering Reference
Accurate induced draft blower sizing combines thermal gas expansion from the calculator above with measured duct velocity pressure, dirty air pollution control (APC) pressure drop, and cold-start density margin.
Before replacing an existing exhaust blower or validating a running furnace line, measure gas velocity in a straight duct section located at least 7.5 equivalent diameters downstream and 3 diameters upstream of elbows or dampers per AMCA Publication 203. An equal-area L-type Pitot-static traverse records local velocity pressure (Pv in mmWC or Pa) across centroid or log-Tchebycheff points. Gas velocity follows V = sqrt(2 * g * Pv / rho_actual) when Pv is in mmWC (or sqrt(2 * Pv_Pa / rho_actual) in Pascals), where rho_actual is flue-gas density at stack temperature and elevation rather than 1.20 kg/m3 ambient air. Multiplying average duct velocity by cross-sectional area gives Actual cubic meters per hour (Am3/hr) directly at blower suction. For step-by-step traverse grids and manometer hookups, see our Pitot-tube airflow and duct static pressure measurement guide.
An induced draft blower pulls negative suction across every upstream process and air pollution control device in series. Total Fan Static Pressure equals the sum of furnace hood or economizer draft loss, cyclone pressure drop (typically 60 to 110 mmWC), pulse-jet baghouse dirty-filter differential (120 to 180 mmWC before pulsing), wet packed-bed scrubber resistance (100 to 250 mmWC), damper drop, and straight duct plus stack discharge friction. Tight bends within three duct diameters of the blower inlet cone swirl flow unevenly into the impeller eye, imposing hidden AMCA Publication 201 System Effect resistance that lowers delivered capacity without changing nameplate RPM. Review our APC exhaust system resistance and retrofit guide alongside our centrifugal blower RFQ datasheet and sizing calculation guide when building pressure budgets.
Because fan absorbed shaft power scales linearly with gas density at constant impeller RPM (BHP = Q * Pt / (102 * 3600 * eta)), a unit engineered for 200 C flue gas (rho ~0.75 kg/m3) draws roughly 60% higher torque during 25 C ambient commissioning or cold purge unless controlled via VFD current limiting or inlet damper closure. Combine calculated operating volume and chemical dew-point data with our flue-gas material selection by temperature guide and complete our ID blower quote checklist for full AMCA/ISO verification.
Technical Standards Referenced: AMCA Publication 201 & 203 (Fans, System Effect and Field Pitot Measurement); Bureau of Energy Efficiency (BEE) Industrial Fan and IE3/IE4 Motor Guidelines; ISO 5801 Aerodynamic Performance Testing.